Kiln Initial Temperature Approach Threshold:
- This can be adjusted to widen or narrow approach window for the burner control as kiln approaches the initial temperature setpoint.
- Larger number: lower overshoot
- Smaller number: higher potential overshoot
- Variable: PIDTempApproach_F
- Use Connect Screen, connect to Kiln Base, and adjust the above Variable in the Public Table of the Base station
HopDropTime_min
- duration the system will hold the Kiln Temp setpoint before re-checking to adjust downward, in AutoTempStage 2.
AutoTempStage
- 0 is initial heat, burner output is fixed, system checks for Kiln Temp to reach Kiln Initial Temp Setpoint
- 1 is Overshoot, burner adjusts to meet Kiln Temp Setpoint, intended to be aggressive
- 2 is Dropping Temp Setpoint, system is periodically adjusting the Kiln Temp Setpoint to meet the target Hop Temp Setpoint
- 3 is Steady State, Kiln Temp Setpoint matches Hop Temp Setpoint